Storage tanks: read in the feed

Inspection · 3 min read

External inspection by the inspector

A qualified inspector, a systematic check, and a written record.

A formal external inspection is done by a qualified tank inspector while the tank is in service. It covers the foundation, shell, roof and fittings, includes thickness measurements, checks the condition of coatings and settlement, and ends with a report that sets what is needed next.

  • Performed by a qualified inspector, usually with the tank in service, at set intervals.
  • Covers foundation, shell, roof, nozzles, appurtenances, coatings, insulation and cathodic protection.
  • Includes ultrasonic thickness measurements on the shell and on the roof where it is safe to test.
  • Ends with findings, calculations and a recommendation for repairs, monitoring and the next inspection.

The external inspection is the formal check on the condition of a tank in service. It is carried out by a qualified inspector, not just by site staff, and it follows a plan so that nothing important is missed.

The inspector begins with the tank's history: drawings, earlier reports, repair records, the product stored and any known issues. Then they walk the tank, examine the foundation and the ringwall, the shell plates and welds, the roof, and every nozzle, manway, ladder and attachment. They check the coating and any insulation, the earthing and cathodic protection where fitted, the venting and the condition of the bund.

Thickness is measured, typically with ultrasonic gauges, at defined locations on shell courses and on the roof where it is safe to access. The values are compared with earlier readings and with the minimum thickness each part needs. The difference, and the rate of change over time, gives the remaining life.

Settlement is checked, often by a survey, and floating roofs and seals are looked at in operation. Anything unusual is investigated further: a suspect area may need extra measurement or an NDE method to confirm what is going on.

The result is a report. It records what was inspected, what was found, what calculations were made, and what is recommended: monitor, repair, or plan an internal inspection. It also says when the next external inspection is due, using the corrosion rate, the remaining life and the limits in the inspection standard.

Good practice

  • Review earlier reports before you go, so you compare like with like.
  • Measure at the same locations as last time, and record exactly where.

Avoid

  • Do not leave findings without a recommended action and a date.
  • Do not skip the roof because access is awkward.

In the field

Start from the history. If the last inspection flagged a patch of thinning, that is your first stop, and your first comparison reading.

Authorized inspector:
a person qualified under the inspection standard to carry out and sign off tank inspections.
UT:
ultrasonic thickness measurement.

Based on: API 653, API 575. A summary for learning. The standard and your site procedures govern.